Product Categories:Data Center Solution
Overview
GQH-IBS The tailed-made
intelligent bus-bar system for data center
Features
1. It adopts the way of over heading bus-bar to supply power, saving plane space and increasing the amount of cabinet.
2. Any place of feeder plug is available for charging, which is
convenient for installation and expansion.
3. Phase modulation technique solves the problem of high zero-point
voltage.
4.
Monitoring lines are designed in the circuit-board way, solving the problem of
maintenance and complicated repair.
5. Mal-preventing locking technology prevents plugging with electricity.
6. Intelligent
detecting monitors current, voltage, power, electrical degree, harmonic wave,
temperature, amount of on-off of every circuit in real time.
Parameter of bus-bar system |
|
Bus-bar rated voltage |
400V/230V |
Bus-bar rated current |
400A/200A |
Frequency |
50Hz/60Hz |
Short-time withstand capacity |
10ka |
Protection class |
IP30 |
Incoming way of bus |
Cable incoming line |
Feeder out-going line |
Standard industrial connector bus socket 1/2/3 outlet |
Rated current feeder box |
Switches of 63A/40A/32A/16A are all available |
Adjustable phase of feeder plug box |
Adjustable A/B/C |
Plugging way |
Oblique cutting |
Busbar material |
Aluminum alloy wire drawing |
Applicable standard |
GB7251.6-2015.GB/T7251.8-2005 |
Application altitude height |
≤2000m |
Type and description of bus-bar components |
||
Name |
Type |
Description |
200A Bus-bar |
iTAC-MX-200A |
200A bus-bar body |
400A Bus-bar |
iTAC-MX-400A |
400A bus-bar body |
200A incoming line box(non intelligent) |
iTAC-JX-200A |
200A incoming line box without intelligent detecting |
200A incoming line box(intelligent) |
iTAC-JXZ-200A |
200A incoming line box with intelligent detecting, front maintenance |
400A incoming line box(non intelligent) |
iTAC-JX-400A |
400A incoming line box without intelligent detecting |
400A incoming line box(intelligent) |
iTAC-JXZ-400A |
400A incoming line box with intelligent detecting, front maintenance |
Feeder plugging box(Three outlets, non intelligent) |
iTAC-KX /3 |
Three single-phase industrial connector bus-bar socket outlets, without intelligent detecting circuit |
Feeder plugging box(Three outlets, intelligent) |
iTAC-KX Z/3 |
Three single-phase industrial connector bus-bar socket outlets, with intelligent detecting circuit |
Feeder plugging box(Two outlets, non intelligent) |
iTAC-KX /2 |
Two single-phase industrial connector bus-bar socket outlets, without intelligent detecting circuit |
Feeder plugging box(Two outlets, intelligent) |
iTAC-KX Z/2 |
Two single-phase industrial connector bus-bar socket outlets, with intelligent detecting circuit |
Feeder plugging box(Single outlet, non intelligent) |
iTAC-KX /1 |
One single-phase industrial connector bus-bar socket outlets, without intelligent detecting circuit |
Feeder plugging box(Single outlet, intelligent) |
One single-phase industrial connector bus-bar socket outlets, with intelligent detecting circuit |
|
Power source plug box |
iTAC-DY |
Switching power supply for intelligent circuit |